Skip to main content
Tonnage Calculator AC Logo

HVAC Duct Size Calculator: Find the Right Duct Size by CFM

Use this free duct sizing calculator to find the correct round or rectangular duct size for your airflow needs. Supports supply and return air, rigid and flex duct, and advanced friction and velocity settings.

Duct Size Calculator

Size ducts by CFM, check existing ductwork capacity, convert round to rectangular, or size return air ducts.

Simple Mode
CFM

Tip: 1 ton of AC ≈ 400 CFM. A typical bedroom needs 100-150 CFM.

Duct Application
Duct Material

Results

OptimalWell-sized for this application
Recommended Round Duct:
10diameter
Rectangular Equivalents:
10″ x 812″ x 812″ x 1014″ x 8
Velocity
733 FPM
Optimal
Noise Level
Normal
Acceptable range
Technical Details
Duct Area:78.5 sq.in.Friction Rate:0.08 in.w.g./100ftPressure Drop:0.02 in.w.g.Total Eff. Length:25 ft
Why this size?

A 10-inch round rigid sheet metal duct is recommended for 400 CFM of supply air. Air velocity of 733 FPM is within the comfortable residential range. This is a planning estimate. A professional Manual D duct design accounts for every fitting, branch, and register in the system.

This result is a planning estimate, not a full Manual D design. If replacing equipment tonnage, verify existing ductwork before reuse.

Do not know your CFM yet? This tool starts from airflow. If all you have is the system tonnage or a room size, work the CFM out first with our HVAC CFM calculator, then come back with that number.

Duct Size Chart by CFM

Below are quick-reference duct sizing charts showing the CFM capacity of standard round duct sizes at different air velocities. These charts help you sanity-check the calculator's results or do a quick mental estimate without running the tool.

Round Duct Size Chart

This table shows the maximum CFM a round rigid duct can carry at three common velocity limits: 700 FPM (quiet residential return), 900 FPM (standard residential supply), and 1,100 FPM (high-velocity commercial). It is a velocity ceiling, not a sizing recommendation, and that is why it does not always agree with the calculator above. The calculator sizes on friction rate, the method a designer actually uses, so it will often pick a duct that ends up running well below the velocity in this table. Read this table as the most a given diameter can carry before it gets noisy, and the calculator as the size to fit.

Duct DiameterArea (sq.in.)CFM @ 700 FPMCFM @ 900 FPMCFM @ 1100 FPM
412.6617996
519.695123150
628.3137177216
738.5187241294
850.3244314384
963.6309398486
1078.5382491600
12113.1550707864
14153.97489621176
16201.197712571536
18254.5123715901944
20314.2152719632400
22380.1184823762904
24452.4219928273456

Rectangular Duct Size Chart

Rectangular ducts are common in tight spaces. This chart shows common rectangular sizes and the round duct each one actually matches. The equivalent is calculated on equal friction, not equal area, so it is always smaller than the raw dimensions suggest, because corner turbulence costs you capacity. The CFM column is the airflow that round equivalent carries at 900 FPM, which is the honest number to compare against the round chart above.

Rectangular Size (W×H)Area (sq.in.)Round Equivalent (equal-friction)CFM @ 900 FPM
8×6487.6280
10×8809.8468
12×89610.7557
12×1012012.0702
14×1014012.9815
16×1016013.7926
16×1219215.11120
18×1221616.01254
20×1428018.21630
20×1632019.51871
24×1638421.32230
24×2048023.92810

Flex Duct vs Rigid Duct CFM Comparison

Flex duct has a corrugated interior that creates significantly more friction than smooth rigid sheet metal. This table shows how much CFM capacity you lose when using flex duct instead of rigid at the same diameter.

Duct DiameterRigid CFM (900 FPM)Flex CFM (effective)CFM Loss% Reduction
61771185933%
831420910533%
1049132716433%
1270747123633%
1496264132133%
16125783841933%
181590106053033%
201963130965433%

Return Duct Size Chart

Return ducts are one of the most commonly undersized elements in residential HVAC. Every size below is the smallest standard duct that keeps the listed airflow at or under 700 FPM, the quiet-velocity limit for return air. The velocity column shows what each size actually runs at, so you can check the sizing rather than take it on faith.

Return CFMReturn Duct SizeVelocity at That SizeApplication
1006509 FPMSingle room return
2008573 FPMLarge room or small zone
40012509 FPMCommon branch return
60014561 FPMMulti-room return
80016573 FPMLarge zone return
100018566 FPMMain return trunk (2 ton)
120018679 FPMMain return trunk (2.5–3 ton)
160022606 FPMMain return trunk (3.5–4 ton)
200024637 FPMMain return trunk (4–5 ton)
240028561 FPMLarge system return (5+ ton)

How to Calculate Duct Size

Whether you use our calculator or work by hand, residential duct sizing starts from a velocity limit. You pick the fastest the air is allowed to move, then size the duct to hold it there. The friction rate is checked afterward. (The related equal-friction method works the other way round, fixing a friction rate first; it is what a full Manual D design uses, and it is also how we convert between round and rectangular shapes.) Here is how the velocity approach works in four steps.

The velocity limits, friction rates, standard size ladders and the equal-friction round-to-rectangular conversion this tool uses are all published in our duct sizing methodology, and the reference tables above render from the same source the calculator does, so a chart can never disagree with the tool.

Step 1: Determine Required Airflow (CFM)

Before sizing any duct, you need to know how much air it must carry. This comes from a Manual J load calculation (you can calculate your required tonnage using our Tonnage Calculator AC) or a simple rule of thumb: approximately 400 CFM per ton of air conditioning. A 3-ton system requires roughly 1,200 CFM of total airflow, which is distributed across all supply ducts in the house. If you already know your tonnage and just want the matching airflow, supply and return sizes without doing the arithmetic, they are tabulated for every size from 1.5 to 5 tons on our AC unit size by tonnage page.

For individual rooms, the CFM requirement depends on the room's cooling/heating load. A typical bedroom might need 100–150 CFM, while a large living room or open kitchen may need 300–500 CFM.

Step 2: Choose Duct Type and Shape

Decide whether you are sizing a supply duct (carries conditioned air to rooms) or a return duct (brings air back to the air handler). Return ducts need lower air velocity to minimize noise at the grille, which usually means they are larger than supply ducts for the same CFM.

Also decide between round and rectangular duct. Round duct is more efficient (less friction per unit of air moved), but rectangular duct fits into tight spaces like floor joists and soffits.

Step 3: Account for Friction, Velocity, and Length

The three key constraints in duct sizing are:

  • Friction rate: The pressure drop per unit length of duct (typically 0.08 in.w.g. per 100 feet for residential systems).
  • Air velocity: How fast the air moves through the duct. Residential supply ducts should stay below 900 FPM; return ducts below 700 FPM.
  • Run length: Longer duct runs accumulate more pressure drop and may need to be upsized.

The required duct area equals CFM ÷ max velocity. Convert that area to a diameter (for round duct) using: D = 2 × √(Area ÷ π).

Step 4: Select the Nearest Standard Size

Ducts come in standard sizes (4″, 5″, 6″, 7″, 8″, 9″, 10″, 12″, 14″, 16″, 18″, 20″, etc.). Always round up to the next standard size. If your calculation says you need a 9.3-inch duct, use a 10-inch duct. Rounding down will create higher velocity, more noise, and more pressure drop than intended. In practice, 6″ is the smallest size worth running as a supply branch: a 5″ branch carrying 100 CFM is already at 733 FPM, so the calculator will not recommend anything smaller.

Duct Size by AC Tonnage

Most people do not arrive with a CFM figure. They arrive with a unit sitting outside and a question about what duct it needs. So here is the whole residential range worked out, using the same 400 CFM per ton the calculator uses. If it is the airflow number itself you are after rather than the duct, our HVAC CFM calculator handles that side.

One thing to hold onto while reading these: supply and return are not the same size for the same system. Supply is sized to 900 FPM and return to 700, so the return always ends up a step or two larger. Making them the same size is one of the most common ways a system ends up starved for air.

Supply and Return Duct Size for a 1.5 Ton Unit

A 1.5 ton system moves about 600 CFM. That takes a 12-inch round supply trunk running at 764 FPM, and a 14-inch return at 561 FPM. In rectangular terms the supply lands near 12×10 or 14×10, and the return near 16×12.

The 12-inch is working fairly hard at 764 FPM. If the run is long or has more than a couple of elbows in it, go to 14-inch on the supply too.

Supply Duct Size for a 2 Ton Unit, and the Return That Goes With It

A 2 ton system is 800 CFM. The supply trunk wants 14-inch round at 748 FPM, and the return wants 16-inch at 573 FPM.

This is where the supply and return gap first becomes obvious. Both are carrying the identical 800 CFM, and the return is still two inches wider, purely because return air has to stay quieter. Put that same 800 CFM through a 14-inch return and it runs at 748 FPM, over the 700 limit, which is precisely what you hear as a rush of air at the return grille.

Duct Size for a 2.5 Ton Unit

2.5 tons is 1,000 CFM, which takes a 16-inch supply at 716 FPM and an 18-inch return at 566 FPM.

Worth knowing here: a 14-inch duct tops out at 962 CFM, so 1,000 CFM misses it by under 40 CFM. If you are stuck with an existing 14-inch trunk and the new unit is 2.5 tons, that is the whole of your problem, and it is a small enough gap that a short run with few fittings will usually cope.

3 Ton Duct Size Where the Trunk Gets Tight

A 3 ton system is 1,200 CFM. Supply stays on 16-inch but now runs at 859 FPM, and the return needs 18-inch at 679 FPM.

Both of those sit right against their ceilings: 859 against the 900 FPM supply limit, 679 against the 700 return limit. So a 3 ton system on 16 and 18 inch has essentially no margin left for a long run or a stack of elbows. This is the most common residential size and also the one most often found running noisy, for exactly that reason. If you have the space, 18-inch supply and 20-inch return is what buys you quiet at 3 tons.

4 Ton Duct Size and the 20 Inch Trap

4 tons is 1,600 CFM. Supply goes to 20-inch at 733 FPM, return to 22-inch at 606 FPM.

This one catches people out, and it is worth spelling out because the same duct gives two different verdicts. At 1,600 CFM a 20-inch duct runs at 733 FPM. That is comfortably inside the 900 FPM supply limit. It is over the 700 FPM return limit. So a 20-inch pipe that is entirely correct on the supply side of a system is undersized on the return side of that same system. Use 22-inch for the return.

5 Ton Duct Size at the Top of Residential

5 tons is 2,000 CFM, which is a 22-inch supply at 758 FPM and a 24-inch return at 637 FPM.

At this airflow most installers stop running one return and split it, which is why the calculator starts recommending multiple return trunks above 1,600 CFM. Two returns beat one 24-inch for two reasons: a 24-inch return grille is a large object to put in a hallway ceiling, and splitting the return lets you pull air from two parts of the house rather than one.

A practical warning if you are reading this because you are upsizing. Going from 3 to 4 tons is not just a bigger box outside; on the numbers above it is a bigger trunk and a bigger return as well, and modifying existing ductwork is one of the line items that most often turns a routine quote into an expensive one. It is worth pricing before you commit, which the HVAC replacement cost calculator lets you do with ductwork included as a separate factor rather than buried in a lump sum.

Maximum Duct Length and Why Long Runs Need a Bigger Duct

Every size on this page assumes the duct is a sane length. Stretch the same duct far enough and it stops delivering its rated airflow, which is why maximum duct length comes up about as often as diameter does.

The number that actually matters is not the straight length. It is total effective length, which is the straight run plus an allowance for every fitting in it. The calculator above takes both, under duct run length and fittings, and reports the total along with the pressure drop it produces.

Fittings dominate that total far more than people expect. A single 90-degree elbow adds roughly 10 to 15 equivalent feet. So a 25-foot run with three elbows in it is not a 25-foot run. It is somewhere between 55 and 70 feet, and it behaves like the longer number.

  • Under 50 ft total effective length: the sizes on this page hold as published.
  • 50 to 75 ft: pressure drop is accumulating. Going up one standard size is worth considering.
  • Over 75 ft: upsizing by one standard size is usually necessary rather than optional.

There is no single maximum duct length that applies to every run, because it depends on how much static pressure your blower has left after the filter and coil take their share. The workable rule is that once total effective length passes 75 feet, size the duct as though it were carrying one step more air than it actually is. Flex duct hits these limits sooner, since it moves about a third less air than rigid at the same diameter.

Duct Size to CFM Reference

If you already have ductwork installed and want to know its airflow capacity, use the reverse lookup approach. The calculator's “Duct Size → CFM” mode does this automatically, but here are the key concepts.

How Much CFM Can a Round Duct Handle?

A duct's CFM capacity is simply its cross-sectional area (in square feet) multiplied by the air velocity. For example, a 12-inch round duct has an area of 0.785 sq ft. At 900 FPM, it moves 707 CFM. At 700 FPM (suitable for return air), it handles 550 CFM.

6 Inch Round Duct CFM: The Smallest Branch Worth Running

A 6-inch round rigid duct carries 177 CFM at 900 FPM and 137 CFM at 700 FPM. In flex it falls to about 118 CFM.

This is the floor for a supply branch. A typical bedroom needs 100 to 150 CFM, which is exactly why 6-inch is the standard bedroom branch in rigid. Watch what happens in flex though: 118 CFM barely covers the bottom of that range, so a bedroom on 6-inch flex is marginal and 7-inch is the honest answer.

7 Inch Round Duct CFM and Why the Size Exists

A 7-inch round duct handles 241 CFM at 900 FPM, 187 CFM at 700 FPM, and roughly 160 CFM in flex.

Seven inch is the size people forget exists, and it is often the right answer. Going 6 to 8 inch means going 177 to 314 CFM, which is a large step to take in one move. Seven inch lands in the middle at 241, and it is the reason a room needing 200 CFM does not have to jump all the way to 8-inch.

8 Round Duct CFM for a Large Room or Two Small Ones

An 8-inch round duct carries 314 CFM at 900 FPM and 244 CFM at 700 FPM, dropping to about 209 CFM in flex.

At 314 CFM this covers a large living room by itself, or two bedroom branches taken off one run. It is also where flex quietly costs you a whole size: 209 CFM through 8-inch flex is less than the 241 CFM a 7-inch rigid delivers.

12 Round Duct CFM Where Branches Become Trunks

The 707 CFM figure above is worth expanding on. At the 1,100 FPM commercial limit the same 12-inch duct reaches 864 CFM, and in flex it drops to 471 CFM.

707 CFM is close to a 1.75 ton system's entire airflow, which is why 12-inch is usually the first size that stops being a branch and starts being a trunk. The 236 CFM that corrugation costs you between rigid and flex at this diameter is more than everything a 6-inch branch carries in the first place.

14 Inch Duct CFM and the Single Central Return

A 14-inch round duct carries 962 CFM at 900 FPM, 748 CFM at 700 FPM, and about 641 CFM in flex.

The useful pairing here is on the return side. 748 CFM at the 700 FPM return limit means one 14-inch return covers a 1.5 ton system's full airflow with room to spare, but stops well short of a 2 ton system's 800 CFM. That one fact settles most of the “is my single central return big enough” question in older houses.

Flex Duct CFM by Size, from 7 Inch to 18 Inch

Flex carries about a third less air than rigid at the same diameter, and the two sizes asked about most sit at opposite ends of that range. A 7-inch flex duct moves roughly 160 CFM against the 241 CFM a 7-inch rigid gives. An 18-inch flex moves about 1,060 CFM against 1,590 CFM rigid.

The rule that falls out of it is easy to carry around. Whatever the rigid answer is, flex needs one standard size larger to do the same job. A 10-inch flex at 327 CFM is about an 8-inch rigid at 314. A 12-inch flex at 471 CFM is about a 10-inch rigid at 491.

How Much CFM Can a Rectangular Duct Handle?

For rectangular ducts, start the same way but do not stop at width × height. A 16×10 duct has 160 square inches (1.11 sq ft), which would suggest 1,000 CFM at 900 FPM, but that ignores the corners. Its equal-friction equivalent is a 13.7-inch round duct, so its realistic capacity is about 926 CFM.

This gap is why the rectangular chart below lists an equivalent diameter for every size. Sizing a rectangular duct on raw area consistently overstates what it delivers, and the error grows with the duct: a 24×20 looks like 3,000 CFM on area but performs like a 23.9-inch round at roughly 2,810 CFM.

24x8 Duct CFM and the Aspect Ratio Problem

A 24×8 duct has 192 square inches, which on raw area suggests 1,200 CFM at 900 FPM. Its equal-friction equivalent is a 14.6-inch round, so the honest figure is about 1,048 CFM. The corners cost you 152 CFM.

24×8 is a 3:1 aspect ratio, which is why the calculator will not offer it as a recommendation. People look this size up because they already have one in a joist bay or a wall cavity, not because anyone specified it. If that is your situation, 1,048 CFM is what you have, and it is enough to serve a 2.5 ton system on the supply side.

20x8 Duct CFM in a Joist Bay

A 20×8 duct is 160 square inches. Raw area claims 1,000 CFM. The equal-friction equivalent is 13.5-inch round, so real capacity is about 892 CFM at 900 FPM and 694 CFM at 700 FPM.

At 2.5:1 this is the other common joist-bay size nobody would specify new, and the numbers show why it survives anyway: 892 CFM covers a 2 ton supply comfortably. The return side is where it bites. 694 CFM is fine for a 1.5 ton system and short of a 2 ton one, so the same duct passes as supply and fails as return on the same house.

14x8 Duct CFM for a Branch Run

A 14×8 duct is 112 square inches and performs like an 11.5-inch round, giving about 644 CFM at 900 FPM and 501 CFM at 700 FPM. Raw area would have told you 700.

At 1.75:1 the shape is reasonable, and this is the size that most often stands in for a 12-inch round where the space is too shallow to take one. Note that it is slightly smaller than the duct it replaces, since a 12-inch round carries 707 CFM, so on a long run treat it as the smaller duct it actually is.

20x20 Duct CFM at the Trunk End of the Scale

A 20×20 duct is 400 square inches. Raw area suggests 2,500 CFM, while its 21.9-inch round equivalent gives about 2,346 CFM at 900 FPM and 1,825 CFM at 700 FPM.

Square is the most efficient rectangular shape, which is why the gap between raw area and real capacity is at its smallest here, around 6 percent. Compare that with 24×8, where the same comparison costs about 13 percent. If you have the depth to make a rectangular duct closer to square, take it, because the aspect ratio costs you more than the size does.

Why CFM Capacity Changes with Friction and Velocity

The numbers above assume specific velocities. In practice, the real CFM through a duct depends on the system's total static pressure and the blower's performance curve. A duct that can carry 707 CFM at 900 FPM might only see 500 CFM if the rest of the system has excessive pressure drop (from dirty filters, restrictive fittings, or undersized returns).

Return Air Duct Size Calculator Guide

Return air is one of the most misunderstood and frequently undersized parts of residential HVAC systems. If you only take one thing from this page, let it be this: the return side matters just as much as the supply side.

Return Duct Sizing Basics

The total return air volume must equal the total supply air volume. If your system delivers 1,200 CFM through all supply registers combined, the return duct system must also be capable of pulling 1,200 CFM back to the air handler. If it can't, the blower starves for air, system efficiency plummets, and the evaporator coil may freeze.

Supply vs Return Sizing Differences

Return ducts need to be physically larger than supply ducts for the same CFM because return grilles are large, exposed openings that create noticeable noise if air velocity is too high. The industry standard is to keep return velocity at or below 700 FPM (compared to 900 FPM for supply). This means a return duct needs roughly 30% more area than a supply duct carrying the same CFM.

Common Return-Air Mistakes

  • Single undersized central return: Many older homes have one central return that is far too small for the system. The fix is adding additional return drops or upsizing the return grille and trunk.
  • Closing off rooms with return air: Closing bedroom doors in a home with a central return can create massive pressure imbalances, making rooms stuffy and straining the system.
  • Using supply duct sizes for returns: A 10-inch supply branch works for 400 CFM, but a 10-inch return branch is too small for 400 CFM. You need 12 inches minimum for quiet return operation at that airflow.
  • Ignoring filter restriction: The return air filter adds significant pressure drop. Size the return duct to accommodate both the duct friction and the filter drop.

Round vs Rectangular Duct Sizing

Square to Round Conversions

Converting between round and rectangular duct sizes requires the equal-friction equivalent diameter formula, not the hydraulic diameter, which is a different quantity and gives a smaller answer. A rectangular duct is never a 1:1 conversion with a round duct of the same numeric dimensions because the corner turbulence in rectangular ducts increases friction. Common conversions include:

  • 12×8″ rectangular10.7″ round (use 12″ if you are replacing it)
  • 14×10″ rectangular12.9″ round
  • 16×12″ rectangular15.1″ round
  • 20×14″ rectangular18.2″ round
  • 24×16″ rectangular21.3″ round

Note the direction of the rounding. When you replace a rectangular duct with round, round up to the next standard size, because rounding down puts you below the capacity you started with.

When to Use Round vs Rectangular Ducts

Round duct is preferred whenever space allows. It has lower friction per square foot of duct area, is easier to seal, and is often cheaper to install. Rectangular duct is used when vertical space is limited (e.g., running through floor joists, above drop ceilings, or in soffits). However, very flat rectangular ducts (like 24×6) have extremely high friction and should be avoided - keep the aspect ratio below 4:1 whenever possible.

Static Pressure, Friction Rate, and Velocity Explained

What Friction Rate Means

Friction rate is the pressure drop per unit length of duct, measured in inches of water gauge per 100 feet of duct (in.w.g./100ft). The standard residential value is 0.08 in.w.g./100ft. Higher friction rates mean you can use smaller ducts, but the blower has to work harder. Lower friction rates mean larger, quieter ducts but higher installation cost.

What Static Pressure Means

Static pressure is the total resistance the blower must overcome to push air through the entire duct system (supply + return + filter + coil + registers). It is measured in inches of water gauge (in.w.g.). A typical residential system is designed for 0.5 in.w.g. total static pressure. If your duct system creates more pressure than the blower can handle, airflow drops and comfort suffers.

Why Undersized Ducts Create Noise and Airflow Problems

When ducts are too small, air velocity increases. High-velocity air creates turbulence at elbows and registers, producing the whistling, whooshing, or rumbling noise that homeowners find unacceptable. Beyond noise, high velocity increases friction, which raises static pressure, which reduces airflow - a vicious cycle that reduces system efficiency by 15–30%.

When Advanced Manual D Design Is Needed

An ACCA Manual D duct design is the gold standard for duct sizing. It accounts for every fitting, branch, register, and duct run in the entire system, plus the blower's performance curve. You should invest in a Manual D if you're building a new home, adding an addition, replacing equipment with a different capacity, or experiencing persistent comfort problems.

Common Duct Sizing Mistakes

Using Square Footage Alone

You cannot size ducts from square footage. Duct size is determined by CFM, which comes from a load calculation (square footage is only one input to a load calculation). Two 2,000 sq ft homes in different climates with different insulation levels will have completely different CFM requirements and duct sizes.

Forgetting the Accessories in the Plan

A bypass humidifier needs its own duct run between the supply and the return, and plenty of people only discover that once the trunk line is already hung and there is nowhere sensible to put it. Decide whether you are fitting one before the sheet metal goes up, not after; our humidifier sizing calculator gives the capacity that run has to serve.

Ignoring Return Air

The most common mistake in residential HVAC. Contractors frequently focus on supply duct sizing and give the return side minimal attention. An undersized return starves the system of air, raises static pressure, reduces efficiency, and often causes the evaporator coil to freeze in cooling mode.

Reusing Old Duct Sizes Without Checking Airflow

When replacing an HVAC system, many homeowners assume the existing ductwork is correctly sized. If the new system has a different capacity than the old one (even just half a ton larger), the old ducts may be inadequate. Always verify duct sizes against the new system's CFM requirements using the calculator above.

Ignoring Fittings and Duct Length

Every elbow, tee, transition piece, and damper in a duct run adds equivalent length - a standard 90° elbow adds about 10–15 equivalent feet. A short duct run with four elbows might have 60+ equivalent feet of length. Failing to account for fittings leads to undersized ducts and excess pressure drop.

Confusing Flexible and Metal Duct Performance

Flex duct is convenient but has roughly 50% more friction than rigid sheet metal. A 10-inch flex duct does not perform like a 10-inch rigid duct - it performs closer to an 8-inch rigid duct. If you're using flex duct, always upsize by at least one standard diameter compared to what a rigid duct calculation recommends.

Frequently Asked Questions

What size duct do I need for 100 CFM?

For 100 CFM of supply air through rigid duct, a 6-inch round duct is sufficient. A 6-inch duct at 100 CFM runs at about 509 FPM, which is well within the quiet range, so the same size also works for return air and for flex duct. Step up to 7 inches only if you want extra margin on a long run. Do not drop to 5 inches - that pushes velocity to 733 FPM.

What size duct do I need for 200 CFM?

A 200 CFM supply run requires a 7-inch round rigid duct, which runs at 748 FPM. An 8-inch duct is the common upsize if you want it quieter. For return air, use an 8-inch duct minimum (573 FPM) to stay below 700 FPM. If using flex duct, step up to at least an 8-inch diameter, since flex carries about a third less air than rigid at the same size.

What size duct do I need for 400 CFM?

For 400 CFM of supply air at standard velocity (900 FPM), use a 10-inch round rigid duct. For return air, use a 12-inch duct. This is the most common question because 400 CFM is the airflow requirement for one ton of air conditioning.

What size duct do I need for 500 CFM?

A 12-inch round duct handles 500 CFM at 637 FPM, which sits inside the limit for supply and return alike. 500 CFM is roughly the crossover point where one size still serves both: below it the return can usually match the supply, and above it the return starts needing to be larger. A 10-inch duct is not an option here, since it tops out at 491 CFM at 900 FPM. The rectangular equivalent is 12×10, which works out to almost exactly a 12-inch round on equal friction.

What size duct do I need for 1000 CFM?

At 900 FPM, 1000 CFM requires a 16-inch round supply duct. A 14-inch duct tops out at 962 CFM, so it is undersized for 1000 CFM. For return air, use an 18-inch round duct. Rectangular equivalents include 18×12 for supply and 20×14 for return. These sizes are typical main trunk lines.

How do I calculate duct size from CFM?

Divide the required CFM by the max air velocity (typically 900 FPM for supply, 700 FPM for return). This gives you the cross-sectional area in square feet. Convert to square inches (multiply by 144), then find the diameter: D = 2 × √(Area ÷ π). Round up to the nearest standard duct size.

How much CFM can a duct handle?

A duct's CFM capacity depends on its size and the acceptable velocity. For example, a 10-inch round duct handles 491 CFM at 900 FPM, and a 12-inch duct handles 707 CFM. You can use our calculator in "Duct Size → CFM" mode to check any size.

What size return air duct do I need?

Return air ducts need to be larger than supply ducts. For a typical 2-ton system (800 CFM), the main return trunk should be at least 16 inches round. For 3 tons (1200 CFM), use an 18-inch minimum (20 inches recommended). Many homes are undersized on returns, which starves the system of air.

How do I size rectangular duct vs round duct?

Use the equal-friction equivalent diameter formula to convert between shapes: De = 1.3 × (Width × Height)^0.625 ÷ (Width + Height)^0.25. This is not the same as matching cross-sectional area - a rectangular duct must have a larger total cross-section than a round duct to move the same air, because corner turbulence adds friction. For example, a 12×8 duct has 96 square inches but performs like a 10.7-inch round duct, which has only 90. Our calculator provides rectangular equivalents automatically.

What friction rate should I use?

The industry standard for residential ductwork is 0.08 in.w.g. per 100 feet. Use a lower rate (0.05–0.06) if noise is a priority (e.g., bedrooms, home offices). Use a higher rate (0.10–0.12) only when space constraints force smaller ducts.

Does flex duct reduce airflow?

Yes. Flex duct has approximately 50% more friction than rigid sheet metal due to its corrugated interior surface. A 10-inch flex duct moves roughly the same air as an 8-inch rigid duct. Always upsize flex duct by at least one standard size compared to rigid.

Can I use the same duct size for heating and cooling?

Usually yes, because both systems need similar airflow rates (about 400 CFM per ton). Size your ducts for whichever system requires more airflow. If you have a heat pump with electric backup heat, the cooling mode typically sets the higher CFM requirement.

What happens if my duct is undersized?

Undersized ducts cause high velocity air, which creates whistling and whooshing noise at registers. The blower motor works harder, increasing energy use. Rooms at the end of long undersized runs won't get enough airflow and will feel uncomfortable. In extreme cases, the evaporator coil can freeze.

How do fittings affect duct size?

Every elbow, tee, transition, and damper adds equivalent length to the duct run. A standard 90° elbow adds 10–15 equivalent feet. If a duct run has 3 elbows, you might add 30–45 feet of equivalent length, significantly increasing pressure drop. Account for fittings by increasing the duct run length in the advanced settings.

Can I reuse existing ductwork with a new HVAC unit?

Maybe. If your new system has the same tonnage as the old one, existing ducts are probably fine. But if you're upgrading capacity (e.g., from 2.5 tons to 3.5 tons), the old ducts may be undersized. Use the calculator to check each duct run against the new CFM requirements before assuming the old ductwork will work.

When is a professional Manual D duct design needed?

You should get a professional Manual D duct design for new construction, major renovations, system capacity changes, or if you have comfort complaints (hot/cold rooms, excessive noise). An online calculator gives excellent ballpark guidance, but a Manual D accounts for every fitting, branch takeoff, and register in the entire system.

How do I calculate return air duct size?

Start with your system's total airflow (tonnage × 400 CFM), then divide by 700 FPM - the maximum quiet velocity for return air - to get the required area, and convert to a round diameter. In practice: a 2-ton system (800 CFM) needs a 16-inch return, a 3-ton (1200 CFM) needs 18 inches, and a 4-ton (1600 CFM) needs 22 inches. Note that a 20-inch duct is not enough for 1600 CFM - it runs at 733 FPM, over the limit. Switch the calculator above to "Return" mode and it applies the lower velocity limit automatically.

What size duct do I need for a range hood or exhaust fan?

Exhaust runs are also sized by CFM, but they tolerate much higher velocity than supply air because the noise ends up outside and the run is short, so these sizes are smaller than the 900 FPM rule would give. Bathroom fans (50-110 CFM) use 4-inch duct, or 6-inch for runs over 25 feet. Range hoods need 6-inch duct up to about 400 CFM, 8-inch for 600 CFM, and 10-inch for 900+ CFM professional-style hoods. Always use smooth rigid duct for kitchen exhaust - flex duct collects grease and chokes airflow - and never downsize below the fan manufacturer's outlet diameter.

Can I calculate duct size from square footage?

Not directly - ducts are sized from CFM, not floor area. Square footage only matters as an input to the load calculation that determines CFM: roughly, home square footage determines tonnage, tonnage × 400 gives total CFM, and each room's share of the load sets its branch CFM. A typical bedroom ends up needing 100-150 CFM (6-inch rigid duct, or 7-inch in flex) regardless of whether the whole house is 1,500 or 3,000 sq ft.